PRODUCTS

HCP.2021/M1001.XS | Configurable 3 Stage Heat Recovery Controller Heat Recovery Control Devices_HCP.2021/M1001.XS | Configurable 3 Stage Heat Recovery Controller

Product Code: HCP.2021/M1001.XS
For more information about the product;

HCP.2021/M1001.XS | Configurable 3 Stage Heat Recovery Controller

HCP.2021/M1001.X | Configurable 3 Stage Heat Recovery Controller


HCP.2021/M1001.X Series heat recovery controllers can be easily connected to building management systems with Modbus-Rtu protocol over Rs-485 line. It is possible to easily control and monitor more than one heat recovery device via any scada, hmi or computer software. It is possible to control the device to the ambient air quality with the 0-10V air quality sensor. With a 0-10V humidity sensor, there is a humidification or dehumidification control output on the device. Various configurations can be made thanks to selectable universal inputs. Easy to use, the user can easily adapt to the device thanks to the Turkish/English menus. Device working/stopping times can be set separately for 7 days a week via the device. Thanks to the key lock feature on the control panel, unauthorized intervention to the device can be easily prevented.


-2 control panels (control card + room control panel)


-Temperature sensor integrated in the room control panel


 -Control with Channel Type Sensor


 -External Sensor Connection (NTC 10K)


 - Possibility to control from BYS system with external sensor without room control panel


 -Aspirator and Fan 3 Level Manual + Automatic Fan Speed ​​Selection


 -Heating Resistance 3 Levels Manual + Automatic Fan Speed ​​Selection


 -Weekly Program (Optional)


 -Blow Temperature Input


 -Outside Air Temperature Input


 - 4 0-10V Output Frequency Inverter (VFD) or Proportional Valve/Heater Drive Feature


 -Filter Dirty Inlet


 -Weekly Program (Optional)


 -On/off control possibility from BYS system (Dry contact)

Technical Specification

Environmental Features
Operation, Storage Temperature0 ... +40°C/0 ... +50°C (without icing and condensation)
Protect ClassAccording to EN 60529 standard Control Card: IP 56/ Room Panel: IP 20
Packet
Mounting Method
DimensionRoom Panel: G86*Y86*D40 / Control Card: L155xW121xH30 mm
WeightRoom Panel: 140 gr Control Card: 362 gr
Electrical Spesification
ControlControl with Panel
Relay Current CapacityVantilator& Aspirator: Max.10A / Heater & Device Working Relay Output: Max.3A
Heat Range
SupplyAC230V ±10% , 50/60 Hz
OutputsVantilator, Aspirator, Heater, Device is running information output
Power Consumption5 VA
ConnectionTerminal Connektor 1,5 mm2